Indoor air quality study for the Norwegian Embassy in Abu Dhabi. NILU OR
NILU has been asked by the Norwegian Embassy in Abu Dhabi to carry out an indoor air quality(IAQ) study. The results have shown that there is a big variation in the temperatures ( ¿10 C) between the monitored locations in the office. Data analysis from employees survey about indoor air have shown that employees do not feel comfortable with the temperature conditions. In addition mould growth was detected in Ambassador¿s office.
CO2 concentration exceeded the acceptable limit in two locations, because the ventilation system is not capable to provide sufficient amount of fresh air to the number of occupants. The conclusion was that the main problem was related to the unbalanced ventilation system creating improper air circulation leading to high CO2 concentrations and large differences in temperatures.